| Products » Dataloggers/Controllers » XPERT TERMINATION BOARDS |
 |
XPERT TERMINATION BOARDS
8080-0003-3, 8080-0002-4,
6461-1239, 6461-1240, 6461-1241, 6461-1242 |
 |
| |
ANALOG
I/O w/TERMINATION 8080-0003-3
|
| Multi-stage
circuitry |
Automatically
resets after surge |
| Operating
temperature |
-40°C
to +60°C |
| Accepts
wire sizes (*input side) |
26-14
AWG |
| Accepts
connection (#output side) |
0.1”
centerline ribbon cable |
| Series
resistance (Analog I/O) |
10
ohms |
| Power
handling |
(8/20
uS) 20 kAmps |
| Clamping
voltage |
36
V |
| Maximum
line voltage (Analog I/O) |
22
V |
| Dimensions |
4.2”
W X 3.1” H |
|
| |
DIGITAL
I/O w/TERMINATION 8080-0002-4
|
Multi-stage
circuitry
|
Automatically
resets after surge |
| Operating
temperature |
-40°C
to +60°C |
| Accepts
wire sizes (*input side) |
26-14
AWG |
| Accepts
connection (#output side) |
0.1”
centerline ribbon cable |
| Series
resistance (Analog I/O) |
10
ohms |
| Power
handling |
(8/20
uS) 20 kAmps |
| Clamping
voltage |
36
V |
| Maximum
line voltage (Analog I/O) |
18
V |
| Dimensions |
4.2”
W X 3.1” H |
|
| |
RS-232
Termination 6461-1239
|
| Accepts
wire sizes (*input side) |
26-14
AWG |
| Accepts
connection (output side) |
DB-9
serial |
| Automatically
resets after surge |
|
Series
resistance (Data lines)
|
100
ohms |
| IEC
61000-4-5 (Lightning) |
(8/20
uS) 12 Amps |
| IEC
61000-4-2 (ESD) |
15
kV (air) |
| Clamping
voltage |
(5
Amps) 24 |
| Maximum
line voltage (Data lines) |
12
V |
| Maximum
line voltage (Power lines) |
24
V |
| Capacitance |
150Pf |
| Dimensions |
1.4”
W X 3.1” H |
Signal
lines available
RXD
TXD |
(input
side)
CTS or DSR (not both)
Pin 9 (power out from Xpert/Xlite)
DTR or RTS (not both) |
|
| |
SDI-12
Termination 6461-1241
|
Multi-stage
circuitry
|
Automatically
resets after surge |
| Operating
temperature |
-40°C
to +60°C |
| Accepts
wire sizes (input/output) |
26-14
AWG |
| Series
resistance (Analog I/O) |
100
ohms |
| Power
handling |
(8/20
uS) 20 kAmps |
| Clamping
voltage |
36
V |
| |
Dual
SDI-12 Input Connections
|
Dimensions
|
1.4”
W X 3.1” H |
|
| |
TELEPHONE
TERMINATION 6461-1240
|
Operating
temperature
|
-40°C
to +60°C |
| Accepts
wire sizes (input side) |
26-14
AWG or RJ-11 telephone jack |
| Accepts
connection (output side) |
RJ-11
telephone jack |
| Multi-stage
circuitry |
Automatically
resets after surge |
| Surge
ratings |
TELCORDIA
GR-1089
ITU K.20/21/45
FCC PART 68 |
| Let
through voltage |
400
V |
| Dimensions |
1.4”
W X 3.1” H |
|
| |
POWER
TERMINATION 6461-1242
|
Accepts
wire sizes (input/output)
|
26-14
AWG |
| Operating
temperature |
-40°C
to +60°C |
| Dimensions |
2.9”
W X 3.1” H |
|
| |
SOLAR
& AC/DC INPUTS
|
Maximum
voltage
|
22
V |
| Transient
Protection |
(10/1000
uS) 1500 W |
| Sense
Output Accuracy |
+2% |
| Output
to Regulator= |
Higher
(V) of Solar or AC/DC |
| Maximum
Current |
5
amps |
| Maximum
Voltage Drop |
0.7
V |
|
| |
REGULATOR
to BATTERY
|
| Current
Sense Resistance |
0.033
ohms |
| Current
Sense Error |
<
5 % @ 3 Amps |
| Battery
Voltage Sense Accuracy |
±
2 % |
 |
SDI-12
Analog Input Module |
|
| |
|